Earth leakage circuit breaker Doepke

Add to selection
General information
Ordercode YESSS
09932111
Product code
09932111
EAN code
4014712222137
Product group
Earth leakage circuit breaker
Brand
Doepke
RCBO 1p+N, 6A, 0.3A, 50Hz, 230V (AC), Type A, B-char. RCBO 1p+N, 6A, 0.3A, 50Hz, 230V (AC), Type A, B-char.
Product description

RCBOs combine residual current and miniature circuit-breakers in a single device (RCBO). They protect people against residual currents and systems against short-circuit and overload. Switches from series DRCBO 3 are independent of the mains voltage and have a high rated switching capacity. Separate displays enable a quick overview of the current operating conditions. DRCBO 3 can be conveniently installed and removed. Type A switches are sensitive to pulsating and alternating currents. This function is independent of the mains voltage. Switches with tripping characteristic B are the standard protection for lighting and socket circuits. Standard switches are designed for electric circuits with a rated voltage of 230 V or 400 V and a rated frequency of 50 Hz. Properties: tripping not dependent on mains and auxiliary voltage; sensitive to AC residual currents and pulsating DC residual currents (type A) compact design for all rated currents; high short-circuit resistance; green/red switching position indicator; residual current tripping indicator; Strain-relief clamps with protection against wires being lodged behind them and wide terminal cross-section range for rail and line wiring on both connection sides; Use of conventional wiring rails possible; Neutral conductor right; tri-stable snap-in slider for easy mounting and removal; high electromagnetic compatibility (immunity to interference for industrial applications) Mounting: quick fastening to mounting rail; any installation position; supply as desired; Application areas: Protection of circuits in residential and purpose-built buildings as well as industrial facilities with TN-S, TT and TN-C-S networks. In IT networks. the RCCB/MCBs can be set to switch off in the event of a second earth fault; Not permitted for use in systems with TN-C networks; not permitted for protecting circuits in which the power electronics equipment may cause smooth DC residual currents or residual currents with frequencies not equal to 50/60 Hz.

Product specifications
Release characteristic
B
Rated current
6 A
Rated fault current
0.3 A
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Width in number of modular spacings
2
Rated voltage
230 V
Number of poles (total)
2
Number of protected poles
1
Rated short-circuit breaking capacity according to EN 61009
10 kA
Leakage current type
A
Rated short-circuit breaking capacity Icn according to EN 61009-1
10 kA
Frequency
50 Hz
Current limiting class
3
Disconnection characteristic
Undelayed
Concurrently switching neutral conductor
Yes
Over voltage category
3
Surge current capacity
0.25 kA
With interlocking device
Yes
Pollution degree
2
Voltage type
AC
Built-in depth
68 mm
Anti-nuisance tripping version
No
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 40 °C
Connectable conductor cross section solid-core
1 - 25 mm²
Connectable conductor cross section multi-wired
1 - 16 mm²
Power loss
0.9 W
more specifications
^