Earth leakage circuit breaker Doepke

Add to selection
General information
Ordercode YESSS
09945107
Product code
09945107
EAN code
4014712266582
Product group
Earth leakage circuit breaker
Brand
Doepke
RCBO 3p+N, 32A, 0.03A, 50Hz, 60Hz, 230/400V (AC), Type A, RCBO 3p+N, 32A, 0.03A, 50Hz, 60Hz, 230/400V (AC), Type A, B-char.
Product description

RCBOs combine residual current and miniature circuit-breakers in a single device (RCBO). They protect people against residual currents and systems against short-circuit and overload. The DRCBO 4 have a rated switching capacity of 6 kA. They provide a labelling area in addition to the tripping indicator. Type A switches are sensitive to pulsating and alternating currents. This function is independent of the mains voltage. Switches with tripping characteristic B are the standard protection for lighting and socket circuits. Standard switches are designed for electric circuits with a rated voltage of 230 V or 400 V and a rated frequency of 50 Hz. Properties: pulsating current-sensitive and AC current-sensitive; mains-voltage-independent tripping; compact design for all rated currents; switch position indicator; separate indication of tripping cause; strain-relief clamps with a wide terminal cross-section range on both connection sides; neutral conductor right; labelling area; Mounting: quick fastening to mounting rail; any installation position; supply as desired; Application areas: Protection of circuits in residential and purpose-built buildings as well as industrial facilities with TN-S, TT and TN-C-S networks. In IT networks. the RCCB/MCBs can be set to switch off in the event of a second earth fault; Not permitted for use in systems with TN-C networks; not permitted for protecting circuits in which the power electronics equipment may cause smooth DC residual currents or residual currents with frequencies not equal to 50/60 Hz.

Product specifications
Release characteristic
B
Rated current
32 A
Rated fault current
0.03 A
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Width in number of modular spacings
4
Rated voltage
400 V
Number of poles (total)
4
Number of protected poles
3
Rated short-circuit breaking capacity according to EN 61009
6 kA
Leakage current type
A
Rated short-circuit breaking capacity Icn according to EN 61009-1
6 kA
Frequency
50/60 Hz
Current limiting class
3
Disconnection characteristic
Undelayed
Concurrently switching neutral conductor
Yes
Over voltage category
3
Surge current capacity
0.25 kA
With interlocking device
No
Pollution degree
2
Voltage type
AC
Built-in depth
68 mm
Anti-nuisance tripping version
No
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 40 °C
Connectable conductor cross section solid-core
1 - 35 mm²
Connectable conductor cross section multi-wired
1 - 25 mm²
Power loss
15.3 W
more specifications
^