RCCB 4p, 16A, 0.03A, Type A, Twin, N left

Add to selection
General information
Ordercode YESSS
2351-9284
Product code
09114810
EAN code
4014712205819
Product group
Residual current circuit breaker (RCCB) with auxiliary device
Brand
Doepke
Type
DFS4 016-4/0,03-A TWIN
RCCB 4p, 16A, 0.03A, Type A, Twin, N left RCCB 4p, 16A, 0.03A, Type A, Twin, N left
STOCK
IN STOCK
0 piece
Product description

Type A residual current circuit breakers are sensitive to pulsating and alternating currents. The twin version offers you the unique option of testing the switch without switching off the circuit. To do this, two complete RCCBs are combined in the device. When the test button is pressed, only one of the switches trips, while the other continues to carry the current and perform the protective function ensuring trouble-free operation. Standard RCCBs are designed for circuits with 230/400 V at 50 Hz.

Product specifications
Number of poles
4
Rated voltage
400 V
Rated current
16 A
Mounting method
DIN rail
Leakage current type
A
Selective protection
No
Short-time delayed tripping
No
Short-circuit breaking capacity (Icw)
10 kA
Rated fault current
0.03 A
Rated switching capacity
0.5 kA
Surge current capacity
0.25 kA
Additional equipment attached at delivery
Protected redundancy circuit
Rated switch current auxiliary device
16 A
Rated voltage auxiliary device
400 V
Degree of protection (IP)
IP20
Width in number of modular spacings
8
Built-in depth
69 mm
Construction size according to DIN 43880
8
Power loss
0.6 W
Ambient temperature during operating
-25 - 40 °C
Connectable conductor cross section solid-core
1.5 - 50 mm²
Connectable conductor cross section multi-wired
1.5 - 50 mm²
Rated insulation voltage Ui
400 V
Rated impulse withstand voltage Uimp
4 kV
Voltage type
AC
With interlocking device
Yes
Frequency
50 Hz
Colour
Grey
RAL-number (similar)
7035
Pollution degree
2
Explosion-proof
No
more specifications
^